The Reading Will Gradually Increase and Stabilize at the True Insulation Resistance. Therefore, the timing of reading is critical

2026 Key Indicators and Purchasing Pitfall Avoidance

Modern insulation resistance testers are highly intelligent and no longer simple crank megohmmeters. When purchasing, pay attention to the following parameters:

Core Parameter Pitfall Avoidance

Table

Focus Point    Pitfall Avoidance Advice    Description

Short-Circuit Current    Recommended > 3mA (even 5mA)    This is the most important indicator! The higher the current, the stronger the load capacity. When testing long cables or large-capacity transformers, charging speed is fast and data is more stable.

Test Voltage    Multiple selectable ranges    Low-voltage equipment (such as 380V motors) select 500V/1000V range; high-voltage cables (above 10kV) need 2500V/5000V/10000V range.

Measurement Range    0 ~ 200GΩ (or higher)    With the advancement of insulation materials, resistance values are getting higher. Too small a range will cause an overflow display (showing 1 or OL) and prevent reading.

Anti-Interference Capability    Must have G terminal (Guard terminal)    Field environments are complex. The G terminal can shield surface leakage current and electromagnetic interference, ensuring that volume resistance rather than surface resistance is measured.

Display Mode    Dual Display (Analog + Digital)    Digital display provides accurate readings, while the analog pointer shows the trend (such as absorption process). The combination of both is most intuitive.