Transformer DC Resistance Quick Tester
Darui Electric recommends:


I. Product Overview
Winding DC resistance measurement is one of the routine tests for transformers. Its main purpose is to check whether the connections between windings and between windings and leads are in good mechanical condition, whether the resistance between phase windings is balanced, and to ensure the safe operation of the transformer.

II. Safety Precautions
1. Please read this manual carefully before using the Transformer DC Resistance Tester.
2. The operator of the Transformer DC Resistance Tester should possess general knowledge of electrical equipment or instrument usage.
3. The Transformer DC Resistance Tester can be used both indoors and outdoors, but should avoid locations exposed to rain, corrosive gases, excessive dust, high temperatures, or direct sunlight.
4. The instrument should be protected from severe vibration.
5. Repair, maintenance and adjustment of the instrument should be performed by qualified personnel.
6. After testing, turn off the power first, then disconnect the test leads.
7. When measuring an off-load tap-changing transformer, be sure to wait until the discharge indicator stops before switching taps.
8. Do not move test clips or power supply wiring during testing.

III. Product Features & Technical Specifications
1. Output Current and Range: Output current: 0-10A, range 100mΩ-30kΩ.
CurrentRangeCurrentRange
10A0.5mΩ-600mΩ0.5A1Ω-12Ω
5A1mΩ-1.2Ω0.2A3Ω-30Ω
2A10mΩ-3Ω20mA25Ω-300Ω
Note: For ranges beyond the above, please use the auto-test function.
2. Test Accuracy: 0.2%, Max Resolution: 0.1mΩ.
3. 65K true color LCD display with Chinese menu prompts for easy operation.
4. Large capacity storage, capable of storing 2000 test records.
5. Power Supply: AC220V±10%.
6. Operating Temperature: -10°C ~ 40°C.
7. Operating Humidity: <80%RH.
8. Instrument Weight: 3kg.



Note: The above information and technical parameters are provided by Yangzhou Darui Electric Co., Ltd.
189527070001
WeChat QR Code
💬
💬 Online Consultation

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
Main Products: Dielectric Loss Tester, Transformer Ratio Tester, Loop Resistance Tester, High-Voltage Wireless Phase Detector, Insulation Resistance Tester, Partial Discharge Tester, Cable Fault Tester, DC Resistance Tester, etc.
Phone: 18952707000 (Manager Guan)Tel: 0514-88770377Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy