Home About Us Products + News + Technical Articles Guestbook Contact Us

Product Details

Partial Discharge Tester - Yangzhou Darui

Partial Discharge Tester-扬州达瑞

Published: 2020-08-22 13:57:16

Views: 2432

Category: Online PD Tester

Product Description
PD Tester
Darui Electric recommends:

  When PD occurs in electrical equipment, EM waves are generated, creating a transient ground voltage signal.Signal strength relates to PD intensity and distance. Special detectors can detect this - these are PD detectors.

Overview
PDdetection product type testing, insulation operation monitoring, etc.
This instrument features high detection sensitivity, wide sample capacitance coverage, broad applicability, complete input unit (detection impedance) configurations, and multiple frequency band combinations (9 types). After proper calibration, it directly reads discharge pulse magnitude with simultaneous pointer and digital display. The pointer display conveniently switches between logarithmic and linear scales. It is a practical PD Tester widely used by power utilities, manufacturers and research institutions.
Main Technical Specifications

1.Testable capacitance range6pF--250μF
2.detectionSensitivity((see Table 1))
3、Amplifier Frequency Band:
①Low-end:10kHz、20kHz、40kHzselectable
②High-end:80kHz、200kHz、300kHzselectable
4、Amplifier Gain Adjustment:6-step coarse adjustment,inter-step gain20±1db;fine adjustment range>20db
Table 1:
Input Unit No.
Tuning Capacitance
Unit
Sensitivity(pC)
(Asymmetric Circuit)
1
6-25-100
pF
0.02
2
25-100-400
pF
0.04
3
100-400-1500
pF
0.06
4
400-1500-6000
pF
0.1
5
1500-6000-25000
pF
0.2
6
0.006-0.025-0.1
μF
0.3
7
0.025-0.1-0.4
μF
0.5
8
0.1-0.4-1.5
μF
1
9
0.4-1.5-6.0
μF
1.5
10
1.5-6.0-25
μF
2.5
11
6.0-25-60
μF
5
12
25-60-250
μF
10
7R
Resistance
 
0.5
5、Time Window:
①Window Width:Adjustable Range15°~150°;
②Window Position:Each window rotatable0°~170°;
③Two time windows can be opened separately or simultaneously。
6、Discharge Meter:
Pointer Display:Logarithmic Scale1-10-100 Error<±5%((relative to full scale))
Linear Scale0-1000 Error<±5%((relative to full scale))
Digital Display:with3&frac12;LEDdigital display0-100.0 Error<±5%((relative to full scale))
7、Elliptical Time Base:
①Frequency50Hz、100Hz、150Hz、200Hz、400Hz
②Ellipse Rotation:with30°per step,capable of120°rotation。
③Display Mode:Ellipse——Line。
④HF time base ellipse adjustable by input voltage (13~275V) to normal size,Power consumption<1VA。
8、Test Voltmeter:
① Range:100kV(expandable)
② Display:3&frac12;digital voltmeter display
Accuracy:better than±5%((relative to full scale))9、Internal、External zero marking
10、Dimensions:500×500×210 mm
11、Weight:approx.18kg


Note: The above information and Technical Parameters are compiled and published by Yangzhou Darui Electric Co., Ltd.
 
18952707000
WeChat QR CodeScan WeChat
💬
💬 Online Consultation

Hello! How can I help you?

Leave a Message
Yangzhou DARUI Electric Co., Ltd.
Main Products: Dielectric Loss Tester, Transformer Ratio Tester, Loop Resistance Tester, HV Wireless Phase Detector, Insulation Resistance Tester, Partial Discharge Tester, Cable Fault Tester, DC Resistance Tester, etc.
☎ Tel: 18952707000 (Manager Guan)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
captcha