WHC-300C Wireless HV Phase Sequence Detector Darui Electric recommends: WHC-300C Technical Parameters 1. Phase Difference Accuracy: Error ≤10°. 2. Frequency Accuracy: ±0.1Hz. 3. Measurable Voltage Range: 6kV-220kV. 4. Transmission Distance: >130m. 5. Phase Sequence: A→B→C 120° apart = positive; otherwise = negative. 6. Phase Detection: ≥30° = out-of-phase; <30° = in-phase. 7. Voice announcement of measurement results. 8. Battery level display; auto power-off after 30min. 9. All three transmitters and the receiver have built-in rechargeable lithium batteries. 10. Leakage current <10μA during HV measurement. 11. Transmitter: <0.1W; Receiver: <0.4W. 12. Operating: -35℃~+45℃, Humidity ≤95%RH. 13. Storage: -40℃~+55℃, Humidity ≤90%RH. 14. Weight: Approx. 6.5kg. 15. Package: 71×35×11cm.
WHC-300C Overview For 3-phase sequence and A/B/C phase difference measurement, also for phase verification. Suitable for 6kV~220kV live-line operation with HV detection. WHC-300C Applications Uses wireless technology for safe, reliable operation. Enables direct HV line phase sequence measurement. Complies with national safety standards. X/Y/Z transmitters send phase/frequency to receiver, which calculates phase differences and determines sequence.
Note: The above information and technical parameters are compiled and published by Yangzhou Darui Electric Co., Ltd.